Fire Properties and Fire Prevention
EnduraFlood components and systems have been tested as shown and installed on this website to ASTM International and NFPA Standards as follows. Purchaser is responsible to use and install EnduraFlood products as shown and as described.
ASTM E84
-
Class A (best available)
-
Flame Spread Index (FSI): 15
-
Smoke Developed Index (SDI): 450
-
Intertek Test Report available upon request
NFPA 286
-
During 40 kW exposure, flames should not spread to the ceiling: PASS
-
The flame shall not spread to the outer extremity of the sample on any wall or ceiling: PASS
-
Flashover, as defined in NFPA 286, shall not occur: PASS
-
The peak heat release rate throughout the test shall not exceed 800 kW: PASS
-
The total smoke released throughout the test shall not exceed 1,000 m2: PASS
-
Intertek Test Report available upon request
DIN EN ISO 11925-2
-
PASS
-
MFPA Test Report available upon request
EnduraFlood components and systems are classified and comply with the following building codes:
IBC - International Building Code
-
Class A (FSI 0-25, SDI 0-450)
-
2603.9 Specific Approval
-
803.1.1.1 Acceptance criteria for NFPA 286
-
803.8.1 Combustibility Characteristics
IRC - International Residential Code
-
R302.9.1 Flame Spread Index
-
R302.9.2 Smoke-Developed Index
- R302.9.4 Alternative Test Method
Florida State Product Approval
-
Rule 61G20-3.001 Scope
-
Florida State Approval not required
DIN EN 13501-1:2019-05
-
Class E
EnduraFlood is NOT FIRE RATED and it should not be used in an application where a fire wall, a fire barrier or a fire partition is required by code. Requirements may vary by local jurisdiction. If you have any questions or concerns about what is required in your specific application, you should always ask your local building official or a licensed contractor.
When using insulation in your wall, EnduraFlood recommends fire-glass batt insulation. When using foam insulation, you may be required to add a thermal barrier between the insulation and your EnduraFlood wall.